- AC/DC/battery power options, UPS battery charger and solar regulator
- Interconnects similar/dissimilar industrial protocols (Master/Slave, Slave/Slave, Master/Master) connecting to databus at full speed (e.g. 12 Mbps Profibus)
- Eight on-board digital I/O which can be configured as either inputs or outputs. Additional internal I/O points include low/normal supply/battery voltage (analog)
- Point to multi-point connectivity with forward error correction, communications integrity check with security encryption
- Online read/write of register I/O, reporting of signal strength (RSSI) with diagnostics including radio path measurement and communications logging
Indicative Applications
|
|
Radio Frequency and TX Power Option Availability
| Frequency | Frequency Band | TX Power | Channel Spacing |
| 400MHz | 360 - 512MHz | 10 - 500mW, 0.5 - 5W | 12.5/20/25KHz |
| 868MHz | 868.525MHz | 500mW | 250KHz |
Note:
Specifications subject to change.
I/O Specifications and Ports
| Digital I/O onboard | Eight non voltage/FET I/O: 30VDC 500mA (D I/O configurable as either inputs or outputs) |
| RS232 Serial Port | 9pin DB9 female connector (used for programming only) 9600 baud, 8 bits, no parity, 1 stop bit |
| RS485 Serial Port | Terminal connector (serial expansion only, cable up to 2000m) 9600 baud, 8 bits, no parity, 1 stop bit |
| Ethernet Port RJ45 connector | 10/100 Mbps transformer isolated interface |
Note:
Specifications subject to change.
General Specifications
| Temperature | -40°C to +60°C |
| Humidity | 0-99%RH Non-Condensing |
| Housing | Extruded aluminium: 130 x 185 x 60mm |
| Mounting | DIN mounting |
| Terminal strip | Removable: up to 2.5mm2 (12 gauge AWG wires) |
| Approvals Safety | EMC FCC Part 15, AS3548, EN 301 489 EN60950 RoHS compliant |
Power Supply Specifications
| Mains supply | 12 - 24VAC/9 - 30VDC: over-voltage/reverse power protected |
| Battery supply | 11.5 - 15.0VDC (battery supply volts internal I/O value) |
| Battery charging circuit | 1.2 - 12AHr batter maximum charge current 0.7 at >12V |
| Solar regulator | Direct connection solar panel (up to 30W)/solar battery 100AHr |
| Loop supply | Internal DC/DC converter: 24VDC 150mA |
| Quiscient current draw | 12V, 150mA: 24V, 90mA: add 5mA per I/O point used |
| Transmission current draw | +12V, 350mA: 24V, 200mA |
Note:
Specifications subject to change.
Radio Transceiver
| Transmit power 400MHz 868MHz | 10 - 500mW, 0.5 - 5W: approved to EN 300 113, EN 300 220 868.525MHz: 500mW |
| Receiver sensitivity 400MHz 868MHz | -112dBm -108dBm: 868.525MHz |
| Line of sight range max* 400MHz 868MHz | 100mW EIRP: to 5km 500mW: to 5km |
| Antenna connector 400MHz 868MHz | BNC female coaxial (with gas discharge arrestor) SMA female (Surge diverter: CSD-SMA-2500 with CCTAIL-SMA-M |
Note:
Specifications subject to change.
• *As with all distances quoted, these are dependant on local terrain/obstacles
Wireless gateways provide connectivity between similar/dissimilar industrial databuses and/or field device I/O (e.g. Ethernet/IP to Profibus, etc.) Connected via RS232/485 and Ethernet, register allocated data-bus values are transmitted/received by radio to and from devices such as PLC's, HMI's, etc.
Flexible by design, Elpro's 105U-G series can multi-hop repeat five times, support a variety of industrial protocols and when combined with Elpro's 1115S and/or I/O products, can create simple to complex I/O products, can create simple to complex I/O networks supporting differing protocols.
Elpro 105U-G-MD1
- Modbus RTU (Master & Slave), DF1
- Up to 4300 I/O points: analog and/or discrete
- Modbus - RS232/485: 300-19200bps
- DF1 (full duplex) - RS232: 300-19200bps